• Addressable Monitor Module

The Fire-Lite MMF-302 Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existing systems.

Features:

  • Supports compatible two-wire smoke detectors
  • Supervises IDC wiring and connection of external power source
  • High noise (EMF/RFI) immunity
  • SEMS screws with clamping plates for ease of wiring
  • Direct-dial entry of address: 01 - 159 on MS-9600 series
  • panels, 01 - 99 on other compatible systems
  • LED flashes during normal operation
  • LED latches steady to indicate alarm on command from
  • control panel

Technical Specifications:

  • Nominal operating voltage: 15 to 32 VDC
  • Maximum current draw: 5.1 mA (LED on)
  • Maximum IDC wiring resistance: 25 ohms
  • Average operating current: 300 uA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol
  • EOL resistance: 3.9K ohms
  • External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum
  • Temperature range: 32 degreesF to 120 degreesF (0 degreesC to 49 degreesC)
  • Humidity range: 10% to 93% noncondensing
  • Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box