The Fire-Lite MS-5UD five zone Fire Alarm Control Panels bring the latest in technology to conventional fire controls

System Capacity
    
Annunciators     8

Electrical Specifications
    
MS-5UD-3
(FLPS-3 Power Supply)     120 VAC, 60 HZ, 1.0 A
MS-10UD-7
(FLPS-7 Power Supply)     120 VAC, 60 HZ, 3.90 A
MS-10UD-7E
(FLPS-7 Power Supply)     240 VAC, 50 HZ, 2.20 A.
Wire Size     minimum 14 AWG (2.0 mm2) with 600 V insulation, supervised, nonpower-limited

Cabinet Specifications     
Door     19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep.
Backbox     19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep.
Trim Ring (TR-CE)     22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Temperature and Humidity Ranges     This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

Write a review

Note: HTML is not translated!
    Bad           Good

5 Zone Conventional Fire Alarm Control Panel - MS-5UD3

  • Product Code: FIRE-LITE:MS-5UD3


Vendor information


0 reviews / Write a review